Ringkasan proyek
Untuk E/I Technical Room di Jangkrik Complex Project Onshore Receiving Facility, Master Marine menyediakan paket HVAC, paket pressurizing fan, exhaust damper, instrumen, dan Honeywell HVAC control panel redundan. Material takeoff diterbitkan untuk konstruksi pada 20 Januari 2019 dalam proyek EPCI Lean Gas Pipeline Phase 1.
Peralatan HVAC
- Three custom stainless-steel split air-conditioning units, each rated at 33,000 Btu/h (3 x 50% redundancy)
- Three AHU evaporator coils with Heresite-coated copper fins and copper tubes
- Three filters, three 800 CFM blower-and-motor assemblies, three SS316L drain pans, three drain pipes, and three SS316L AHU casings
- Three 125 x 125 x 75 mm AHU junction boxes, three Danfoss TEN 5 thermal expansion valves for R134a, and three SS316L nameplates
- Three 33,000 Btu/h ACCU condenser coils with Heresite-coated copper fins and copper tubes
- Three Vanco VAD 500 axial fans, each 3,250 CFM, Zone 2
- Three Baldor M7014T motors with SS316L, 1.5 mm bodies
- Three Master Marine ACCU casings with skids, suitable for R134a compressor refrigerant suction
- Three Danfoss MTZ72HN4AVE compressors with refrigerant discharge pressure indicators
- Three REFCO low-side pressure gauges and three REFCO high-side pressure gauges, ATEX Category 2, Zone 1
- Three Danfoss RT1AE and three Danfoss RT5E pressure switches
- Three lots of R134a refrigerant charge, two Crouse-Hinds GUAX junction-box sets, and three SS316L nameplates
Pressurizing and exhaust systems
- One SS316L, 1.5 mm, single-skin Master Marine pressurizing-fan casing with skid
- One Wozair MFD SS316L air-intake damper, 400 x 400 x 300 mm, electric Zone 1 type, with local open/close status indication
- One Veotec SE2 coalescer/moisture eliminator with filter-clog indicator and two-stage coalescer/bag filtration
- One Camfil AeroPleat G4 pre-filter and one Camfil Opakfil ES 4V F9 after-filter
- Two Dwyer 1950-5-1F and two Dwyer 1950-1-2F explosion-proof differential pressure switches
- Two Wozair MFD SS316L motorized shut-off dampers, electric Zone 1 type, 1,400 CFM at 500 Pa, with local open/close indication
- Two Vanco VBD 200 centrifugal blowers and two Baldor centrifugal blower motors
- Two Wozair SS316L non-return dampers, 400 x 400 x 250 mm, and two manual volume dampers
- One Wozair MFD SS316L fire-and-gas damper, electric Zone 1 type, with local open/close indication
- One Dwyer V4-SS-2-U SS316 airflow switch, Zone 1
- One Honeywell 30-3013 analog-output smoke detector, Zone 1
- One Wozair SS316L pressure-relief damper, gravity operated, electric Zone 1 type
- One SS316L Master Marine nameplate for the pressurizing-fan unit
HVAC control panel
The single-door, floor-standing HVAC control panel is a Master Marine panel with a 2,000 x 800 x 600 mm enclosure, IP40 rating, aluminium 6063-T6 extrusion frame, SPCC steel doors and cover, 2.5 mm SPCC mounting plate, continuous polyurethane gasket, textured RAL 0732 powder coating, rear cover, top cover, horizontal punch section, 100 mm plinth, gland plates, and eye bolts.
- One panel enclosure and one lot of control-panel accessories
- Two panel fans with filters and two filtered panel intake openings
- One key selector switch for Local/Remote operation and one emergency-stop button for manual HVAC shutdown
- One Honeywell HCiX 15-inch touchscreen HMI
- Two Honeywell HC900C75-0360-00 redundant C75 CPUs, each with a dedicated communication port
- One 900RR0-0101 redundant CPU rack and one 900RSM-0101 CPU switch module
- Two 900P02-0101, 28 W power supplies
- One 90R12R-0200 12-I/O rack with redundant power
- Two 900P01-0101, 60 W power supplies
- One 900PSM-0101 redundant I/O scanner
- One 900S75-0360 analog-input/analog-output module: 16 analog inputs and 8 analog outputs
- Two 900A16-0101 digital I/O modules: 24 Vdc, 32 digital inputs and 16 digital outputs
- Two 900B08-0202 low-voltage, 36-position Euro-type terminal blocks
- Two 900G32-0101 redundant RTP assemblies and two 3 m prefab cables for 16-channel analog inputs
- Two 900H02-0102 redundant RTP assemblies and two 3 m prefab cables for 8-channel analog outputs
- Four 900TEK-0101 redundant RTP assemblies and four 3 m prefab cables for 32-channel digital inputs
- Four 900TCK-0101 redundant RTP assemblies and four 3 m prefab cables for 16-channel digital outputs
- One UL16AI-RED, one UL08AO-RED, one UL32DIFI-RED, and one UL24D16DO-RED redundant I/O cable assembly
- Two CBLD37HC16AI cables, two CBLD25HC16-A cables, two CBLD25HC16-B cables, two CBLD37HC32DI cables, and one each of CBLD25H32DO-A and CBLD25H32DO-B
- One Experion HS SCADA software package for Windows 7 with point runtime
Instruments and electrical accessories
- One Dwyer HHT-IT-LCD temperature and humidity indicating transmitter with pressure differential indication
- One Dwyer ISDP-004 pressure differential indicating transmitter
- One lot of Hawke cable and cable-gland accessories
- One lot of Master Marine MCT cable-penetration isolators
- Electrical integration of the HVAC equipment, pressurizing fan, dampers, motors, switches, detectors, transmitters, HMI, redundant controller, I/O modules, terminal blocks, SCADA interface, junction boxes, and cable-entry system into the custom control panel