Ringkasan proyek
Master Marine menyediakan dua HVAC control panel berbasis PLC untuk peningkatan Fuel Oil Complex: satu panel untuk FOC-1 dan satu panel untuk FOC-2.
HVAC control panel FOC-1
- Jumlah: 1 unit
- Tipe enclosure: enclosure NOBI floor-standing
- Perlindungan enclosure: IP54
- Sistem kontrol: kontrol berbasis PLC Schneider
- Antarmuka operator: HMI Schneider 10 inci
HVAC control panel FOC-2
- Quantity: 1 unit
- Enclosure type: floor-standing NOBI enclosure
- Enclosure protection: IP54
- Control system: Schneider PLC-based control
- Operator interface: Schneider 10-inch HMI
Control-panel material takeoff summary
- 2 floor-standing HVAC control panels in total
- 2 Schneider PLC-based control systems
- 2 Schneider 10-inch HMIs
- 2 IP54 NOBI enclosures
Complete instrument and equipment takeoff
The following items are transcribed from the FOC-1 and FOC-2 material-takeoff documents. Quantities are shown per area as listed in the documents.
FOC-1 basement and control room
- HVAC unit AHU: 2 units, Master Marine, 750,000 Btu/h each
- HVAC unit ACU: 6 units, Master Marine, 250,000 Btu/h each
- Room humidity and temperature transmitter: 1 EA, Dwyer, model WHT-311
- Room differential pressure transmitter: 1 EA, Dwyer, model MS-021
- DPS filter sensor, 50–500 Pa: 2 EA, Dwyer, model ADPS-03-2-N
- Gas detector: 1 EA, Honeywell, type SPXCDALMPX
- Gas/smoke damper: 1 EA, Wozair, MFD Series, SS316L 2 mm, explosion-proof actuator, fusible bulb 74°C, fail-safe closed
- Motorized volume control damper: 2 EA, Wozair, VCD Series, SS316L 2 mm, explosion-proof actuator, Class 1 Division 2
- Electric dehumidifier: 2 EA, Master Marine, hot-gas model, Class 1 Division 2 solenoid valve
- Control cable: 1 lot, Jembo or equivalent, instrument to HVAC control panel, armoured cable to UL/IED standard
- Power cable: 1 lot, Jembo or equivalent, HVAC equipment AHU/ACU to HVAC control panel, armoured cable to UL/IED standard
- Installation material: 1 lot, Dupont or equivalent R407C refrigerant, refrigerant piping, PVC drain pipe, and insulation
- Fresh-air ducting: 1 lot, Master Marine
FOC-1 ex-laboratory room
- HVAC unit AHU: 1 unit, Master Marine, 500,000 Btu/h
- HVAC unit ACU: 2 units, Master Marine, 250,000 Btu/h each
- Room humidity and temperature transmitter: 1 EA, Dwyer, model WHT-311
- Room differential pressure transmitter: 1 EA, Dwyer, model MS-021
- DPS filter sensor, 50–500 Pa: 1 EA, Dwyer, model ADPS-03-2-N
- Gas detector: 1 EA, Honeywell, type SPXCDALMPX
- Gas/smoke damper: 1 EA, Wozair, MFD Series, SS316L 2 mm, explosion-proof actuator, fusible bulb 74°C, fail-safe closed
- Electric dehumidifier: 2 EA, Master Marine, hot-gas model, Class 1 Division 2 solenoid valve
- Control cable: 1 lot, Jembo or equivalent, instrument to HVAC control panel, armoured cable to UL/IED standard
- Power cable: 1 lot, Jembo or equivalent, HVAC equipment AHU/ACU to HVAC control panel, armoured cable to UL/IED standard
- Installation material: 1 lot, Dupont or equivalent R407C refrigerant, refrigerant piping, PVC drain pipe, and insulation
- Fresh-air ducting: 1 lot, Master Marine, including return-air duct and supply-air duct
FOC-2 basement switchgear room
- HVAC unit AHU: 2 units, Master Marine, 400,000 Btu/h each
- HVAC unit ACU: 4 units, Master Marine, 200,000 Btu/h each
- Room humidity transmitter: 1 EA
- Room temperature transmitter: 1 EA
- Room differential pressure transmitter: 1 EA
- DPS filter sensor, 50–500 Pa: 2 EA, IP54/CE
- Gas detector: 1 EA, Honeywell or equivalent, type XCD or equivalent
- Gas/smoke damper: 1 EA, Wozair, MFD Series, SS316L 2 mm, explosion-proof actuator, fusible bulb 74°C
- Motorized volume damper: 2 EA, Wozair, MFD Series, SS316L 2 mm, explosion-proof actuator, Class 1 Division 2
- Electric dehumidifier: 1 EA, Class 1 Division 2
- Control cable: 1 lot, instrument to HVAC control panel, armoured cable to UL/IED standard
- Power cable: 1 lot, HVAC equipment AHU/ACU to HVAC control panel, armoured cable to UL/IED standard
- Installation material: 1 lot, Dupont or equivalent R407C refrigerant, refrigerant piping, PVC drain pipe, and insulation
- Fresh-air ducting: 1 lot, Master Marine, carbon steel 2 mm, hot-dip galvanized 45 micron finish
FOC-2 control room
- HVAC unit AHU: 2 units, Master Marine, 550,000 Btu/h each
- HVAC unit ACU: 4 units, Master Marine, 275,000 Btu/h each
- Room humidity transmitter: 1 EA
- Room temperature transmitter: 1 EA
- Room differential pressure transmitter: 1 EA
- DPS filter sensor, 50–500 Pa: 2 EA, IP54/CE
- Gas detector: 1 EA, Honeywell or equivalent, type XCD or equivalent
- Gas/smoke damper: 1 EA, Wozair, MFD Series, SS316L 2 mm, explosion-proof actuator, fusible bulb 74°C
- Motorized volume damper: 2 EA, Wozair, MFD Series, SS316L 2 mm, explosion-proof actuator, Class 1 Division 2
- Electric dehumidifier: 1 EA, Class 1 Division 2
- Control cable: 1 lot, Jembo, instrument to HVAC control panel, armoured cable to UL/IED standard
- Power cable: 1 lot, Jembo, HVAC equipment AHU/ACU to HVAC control panel, armoured cable to UL/IED standard
- Installation material: 1 lot, Dupont or equivalent R407C refrigerant, refrigerant piping, PVC drain pipe, and insulation
- Fresh-air ducting: 1 lot, Master Marine, GI 2 mm, hot-dip galvanized 45 micron finish
FOC-2 meeting room
- HVAC unit AHU: 1 unit, Master Marine, 75,000 Btu/h
- HVAC unit ACU: 1 unit, Master Marine, 75,000 Btu/h
- Room humidity transmitter: 1 EA
- Room temperature transmitter: 1 EA
- Room differential pressure transmitter: 1 EA
- DPS filter sensor, 50–500 Pa: 1 EA, IP54/CE
- Gas detector: 1 EA, Honeywell or equivalent, type XCD or equivalent
- Gas/smoke damper: 1 EA, Wozair, MFD Series, SS316L 2 mm, explosion-proof actuator, fusible bulb 74°C
- AC ceiling duct: 1 lot, model not specified, 7,500–764,000 Btu/h capacity range, supply/return air and grille
- Control cable: 1 lot, instrument to HVAC control panel, armoured cable to UL/IED standard
- Power cable: 1 lot, HVAC equipment AHU/ACU to HVAC control panel, armoured cable to UL/IED standard
- Installation material: 1 lot, Dupont or equivalent R407C refrigerant, refrigerant piping, PVC drain pipe, and insulation
- Fresh-air intake and pressurizing fan: 1 lot, BJLS, including return-air duct and volume damper
Additional FOC-2 panel instrument
- Pressure gauge: 0–0.5 in. WC, listed with the FOC-2 HVAC control panel